IBM Cloud Docs
Power requirements

Power requirements


IBM Power Virtual Server Private Cloud: On-premises


Your On-premises site for IBM® Power® Virtual Server must be provisioned with A-side and B-side power redundancy that meets the Power Virtual Server rack connector and load requirements. Table 1 shows the rack connector and load requirements.

Be sure to read all caution and danger statements provided in the Safety notices before you perform the procedures. For more information about safety notices containing the caution and danger information, see Safety notices. Read any additional safety information that comes with your system or optional device before you install the device.

Rack connectors with load capacity requirements
Corresponding PDU Rack line cord feature code Wall plug Rated voltage (V AC) line to line Phase Rated amperage Location
ECJJ (C19) and ECJN (C13) #6492 IEC 60309, 2P+G, 60 A 200 - 240 V 1 48 A US, Canada, Latin America(LA), and Japan
#6491 IEC 60309, P+N+G, 63 A 230 V 1 63 A EMEA
#6489 IEC 60309, 3P+N+G, 32 A 380 – 415 V 3 Wye 32 A per phase Europe, Middle East, and Asia (EMEA)
#6667 PDL 380 – 415 V 3 Wye 32 A per phase Australia and New Zealand
#6653 IEC 60309, 3P+N+G 380 - 415 V 3 Wye 16 A per phase Switzerland
#ELC2 IEC 60309, 3P+N+G, 30 A 380 - 415 V 3 Wye 30 A (derated to 24 A) per phase United States, Canada, Mexico, and Japan (European Style Power for US type countries)
ECJL (C19) and ECJQ (C13) #ECJ6 CS8365C 200 - 240 V 3 Delta 50 A or line (40 A derated) United States, Canada
#ECJ7 IEC 60309, 3P+G 200 - 240 V 3 Delta 60 A or line (48 A derated) United States, Canada, Latin America, and Japan

Table 2 shows the number of PDUs and the corresponding power cords that are required for different configurations.

If you have selected the configuration with 4 PDUs, you can include 6 power drops in the facility plan to increase the number of PDUs in future.

PDUs and power drops requirements
Rack type PDU feature codes Number of PDUs Number of Power S1022 servers Number of Power E1050 servers Number of Power S1022 and E1050 servers Number of Power E1080 servers
(no mixing)
ESMP (Small) ECNJ or ECJQ**
(Default)
4 8 x S1022 (includes management server) N/A N/A N/A
6 3 extra S1022 (C19 PDUs are required) N/A N/A
ECJJ or ECJL** 4 1 (management server) 3 N/A N/A
6 2 x S1022 that is equivalent to 1 MRX. (Optional) 5 2 x S1022 that is equivalent to 1 MRX. N/A
EMPD + 4651 or 4652
(Medium rack 1 or 2)
ECJJ or ECJL** 4 6 3 2 x S1022 that is equivalent to 1 MRX. 1x2 enclosures
6 8 4 2 x S1022 that is equivalent to 1 MRX. N/A
EMPD + 4653 or 54
(Medium rack 1 or 2)
4 8 3 N/A 1x2 enclosures
6 12 4 N/A 2x2 enclosures

** You can place an order for ECJJ or ECJL PDUs only if there is an order with ER3E identifier (specifies 9043-MRX) or EN31 identifier (specifies 4983-AH8).

For more information about IBM power cords, see Supported PDU power cord.

Power calculators: The IBM Systems energy estimator is a web-based tool for estimating power requirements for IBM systems. This tool estimates typical power requirements (watts) for a specific system configuration under normal operating conditions.