Power requirements

Power requirements

Your on-premises site for IBM Storage Ceph as a Service must be provisioned with A-side and B-side power redundancy that meets the IBM Storage Ceph as a Service rack connector and load requirements. Table 1 shows the rack connector and load requirements.

Be sure to read all caution and danger statements provided in the Safety notices before you perform the procedures. Read any additional safety information that comes with your system or optional device before you install the device.

Rack connectors with load capacity requirements
Corresponding PDU Rack line cord feature code Wall plug Rated voltage (V AC) line to line Phase Rated amperage Location
ECJN (C13) #6492 IEC 60309, 2P+G, 60 A 200 - 240 V 1 48 A US, Canada, Latin America(LA), and Japan
#6491 IEC 60309, P+N+G, 63 A 230 V 1 63 A EMEA
#6489 IEC 60309, 3P+N+G, 32 A 380 – 415 V 3 Wye 32 A per phase Europe, Middle East, and Asia (EMEA)
#6667 PDL 380 – 415 V 3 Wye 32 A per phase Australia and New Zealand
#6653 IEC 60309, 3P+N+G 380 - 415 V 3 Wye 16 A per phase Switzerland
#ELC2 IEC 60309, 3P+N+G, 30 A 380 - 415 V 3 Wye 30 A (derated to 24 A) per phase United States, Canada, Mexico, and Japan (European Style Power for US type countries)
ECJQ (C13) #ECJ6 CS8365C 200 - 240 V 3 Delta 50 A or line (40 A derated) United States, Canada
#ECJ7 IEC 60309, 3P+G 200 - 240 V 3 Delta 60 A or line (48 A derated) United States, Canada, Latin America, and Japan